H1Z2Z2-K, optimized version
H1Z2Z2-K/EN 50618 solar cable, can be buried: impact/crushing resistance, AD8, Dca
H1Z2Z2-K - networked photovoltaic (PV)/ solar cable according to EN 50618, UV/ozone resistant, UL crushing &impact resistance test, AD8, burialable, CPR Dca
AD8 - permanent immersion
Can be buried according to test
Dca-classified according to CPR (BauPVO in DE)
Product information
H1Z2Z2-K, optimized version
PV systems with DC system voltage up to max. 1800 V to earth
AD8: Water contact or permanent immersion up to max. 1 meter water depth
Increased mechanical robustness, e.g. B. in case of shock
Burial in a professionally executed cable trench (see Section 4.2 in VDE 0891-6 or Section 300.5 in Article 300 in
NFPA 70/ NEC - National Electrical Code of the USA) with or without an additional, burial protective system such as hose/ pipe
When using an additional, buried protection system, accumulations of contaminated
water in the protection system must be prevented.
Product features
Weather/ UV-resistant according to EN 50618/ VDE 0283-618, Appendix E, as well as ozone-resistant according to EN 50396
Cross-waterproof "AD8" according to IEC 60364-5- 51/ HD 60364-5-51/ VDE 0100-510, IEC 62440 and EN 50525-2-21/ VDE
0285-525-2-21 up to 1 meter water depth
Flame-retardant according to IEC 60332-1-2 as well as Dca-classified according to EU-BauPVO - European Construction Products Regulation (EU) No.
305/2011 [CPR - Construction Product Regulation]
Halogen-free according to IEC 60754-1 (proportion of gases containing halogen acid),
Low corrosivity of the Combustion gases according to IEC 60754-2 (degree of acidity)
Good notch and abrasion resistance
Tested according to underground mechanical UL 854 tests impact resistance and crushing resistance
Standard references / approvals
Type-certified H1Z2Z2-K according to EN 50618
Versions with other cross-sections on request
Structure
Fine-wire, tinned copper conductor
Core insulation made of cross-linked copolymer
Outer sheath made of cross-linked copolymer
Sheath colour: black, red or blue
Other individual colors for the outer jacket on request
Technical data
Classification ETIM 5: ETIM 5.0 Class-ID: EC001578
ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6: ETIM 6.0 Class-ID: EC001578
ETIM 6.0 Class-Description: Flexible cable
Conductor structure: Fine wire according to VDE 0295,
Class 5 / IEC 60228 Cl.5
Minimum bending radius: 4 x OD
Nominal voltage: AC U0/U: 1.0/1.0 kV
DC U0/U: 1.5/1.5 kV
Max. permissible DC system voltage: 1.8 kV
Test voltage: AC 6500 V
DC 15000 V
Ampacity: According to EN 50618, Table A.3
According to EN 50618 with reduction factors for H&umaulage in
routing according to... HD 60364-5-52
Temperature range: >Conductor, max., according to EN 60216-1/ VDE 0304-21: 120°C
Conductor, max., short circuit/earth fault (duration max. 5 s): 250°C
Ambient, min ., permanently installed: -40°C
environment, min., moved or when installed: -25°C
environment, max., in conjunction with EN 60216-1/ VDE 0304-21: 90°C